REFERENCE CONDITIONS Ambient Temperature: 73_F(23_C)_ 4_F(2_C) Relative Humidity: 45 to 55% Measurement Magnitude Frequency: 45-65 Hz (voltage measurements) Line Voltage Waveform: Sine, deviation between effective and rectified value < .5% BatteryVoltage:9V_ .5V Operating Position: Horizontal ELECTROMAGNETIC COMPATIBILITY EMC Interference Emission: EN 50081-1: 1992 Interference Immunity: EN 50082-1: 1992 ELECTRICAL SAFETY Designed to IEC 1010-1 Protection Class: II Test Voltage: _ 5.55Kv Overvoltage Classification: II Pollution Degree: 2 Protection: Housing IP52 AMBIENT CONDITIONS Operating Temp. Range: 32_F(0_C) to104_F(40_C) Storage Temp. Range: -4_F(-20_C) to140_F(60_C)(without batteries) Relative Humidity: Max. 45-55%, condensation must be avoided MECHANICAL DESIGN Dimensions: W 6.50” (165mm) x D 4.33” (110mm) x H 4.92” (125mm) Weight: 3.5 lbs. (1.6kg) (with batteries) POWER SUPPLY Standard or Storage Battery: 6 ea. 1.5V “D” size batteries WorkingRange:7V to10V BatteryServiceLife: Numberof possible measurements with 1 set of “D” size batteries (with lamp in test prod switched off): at least 3,000 measurements of an insulation resistance of 1M_ (NominalVoltage of1000 V, 5 sec. Measurement duration, switched off for 25 sec. etc.) |